Most of the heat-pump disappointments we are called out to in Lancashire are not heat-pump problems at all. The unit is fine; the radiators were chosen for a boiler running at 70°C and are now being asked to heat the same rooms with water at 45°C. This guide clears up the myths about heat loss that cause that mistake and shows how to choose radiators, with aluminium as the first thing to look at, so the heat pump is comfortable and cheap to run. Written by the Gas Safe registered heating engineers at Bradley's Radiators, Blackburn. Last reviewed 1 November 2026.

Every radiator in a UK catalogue is rated at ΔT50: water in the radiator averaging 70°C in a room at 20°C, which is what a gas boiler delivers. A heat pump is designed to run far cooler, typically 40–50°C mean water, because that is where it is efficient. A radiator's output falls faster than the temperature does (the relationship in EN 442 uses an exponent of 1.3), so at ΔT30 — 50°C mean water — the same radiator gives about half its catalogue figure. At 45°C it gives about 41%, at 40°C about 30%. Nothing about the room has changed; the radiator has simply been turned down.

That single fact is behind every myth below. Hold on to it and the rest of the decision becomes straightforward.
Reality: it is big enough at 70°C. A radiator that just copes on a cold January evening with a boiler will deliver roughly half the heat once the heat pump is in, and the room will sit three or four degrees short of comfortable. The test is not whether the room is warm today; it is whether the radiator's ΔT30 output meets the room's heat loss. Every product page on this site shows the ΔT50 figure for each size; halve it and compare that with the room.
Reality: heat loss is a property of the room. It is set by the walls, the glazing, the floor, the roof and how much air leaks in and out, and it is worked out room by room (your MCS installer must do this to BS EN 12831 to qualify for the Boiler Upgrade Scheme). In a well-insulated modern house it is often 40–60W per square metre of floor; in a solid-walled Victorian terrace it can be 100W per square metre or more. The heat pump has to supply that total; each radiator has to deliver its room's share at the design flow temperature. A 7kW heat pump feeding radiators that can only shed 4kW at 45°C will run and run without ever catching up.
Reality: the opposite. Oversizing the radiators is what lets the installer design the system at a lower flow temperature, and every degree the flow comes down improves the heat pump's efficiency by roughly 2–3%. A system designed at 45°C instead of 55°C can use around a fifth to a quarter less electricity for the same warmth. The radiator itself uses no energy; it is only the surface that hands the heat into the room. More surface, cooler water, cheaper heat. For a deeper dive see why bigger radiators matter more than most people realise.
Reality: the room-by-room survey is designed around an outside temperature of about −3°C and the room at 18–21°C, which is what you need on the handful of nights a year the heating is working hardest. It is not a worst case to be trimmed; it is the design condition. Where people get caught is the other way round: they size from the ΔT50 column of a brochure (or an old boiler-era rule of thumb like "1,000 BTU per 50 square feet") and forget to halve it. Our heat-pump radiator sizing guide walks through the worked example; the radiators by heat output pages let you shop by the figure once you have it.
Reality: size is the first test, but the material decides how the radiator behaves on a heat pump, and this is where aluminium earns its place.
Two practical notes. Aluminium needs a corrosion inhibitor rated for mixed-metal systems and a pH-neutral system water; your installer will dose it as a matter of course (it is standard practice on any sealed system). And because the connections sit at a different depth from a steel panel, check the wall-to-pipe-centre measurement as well as the width when you are swapping like for like.
Reality: an infrared panel turns one unit of electricity into one unit of heat; a heat pump turns one unit into three or four. On the same tariff, heat from an infrared panel costs roughly three times as much per kilowatt-hour as heat from the pump, so putting panels in to make up for undersized radiators is paying the premium every hour the heating is on. Where infrared does earn its keep is the room that is not on the heat-pump circuit at all: a garden office, a conservatory, a cloakroom with no pipework, or as a quick top-up in a bathroom. We cover the cases in when we recommend infrared heating instead of a heat pump, and the panels themselves are in our infrared heating range.
Reality: you keep the ones that pass the ΔT30 test and change the ones that do not. In a typical 1990s semi that is one or two radiators in the biggest rooms; in a solid-walled Victorian house it may be most of them. The survey tells you which. Our guide on keeping your existing radiators with a heat pump shows how to read the result, and where a radiator has to change, the pipe-centre finder lists every replacement that drops onto the existing pipes so the pipework stays where it is.
All in stock, with the ΔT50 output shown for every size on the product page. The heat-pump figure below is the ΔT50 output halved — what the biggest size in the range gives at 50°C mean water.

Carisa Nemo XL Double, horizontal
280–565mm high, 800–1,800mm wide. Up to 6,447 BTU (1,891W) at ΔT50, about 975W on a heat pump. The under-window workhorse. From £359.35.

600mm high, 470–1,800mm wide. Up to 4,888 BTU (1,433W) at ΔT50, about 740W on a heat pump. The best-value aluminium panel we sell. From £213.53.

1,800mm high, 295–595mm wide. Up to 3,918 BTU (1,148W) at ΔT50, about 590W on a heat pump, from a wall only 595mm wide. From £251.47.
Need more than one of these can give? Two matching verticals either side of a window, or the Carisa Tallis XL at 1,238W (about 640W on a heat pump) across a 1,800mm wall, usually beats one oversized unit. The full range, with every size and output, is under aluminium radiators.

No. Keep every radiator whose output at ΔT30 (about half its catalogue figure) meets the room's heat loss, and change the rest. The room-by-room survey decides; in most houses it is a minority of rooms.
Yes, and they are our first recommendation: fast response, low water content, high output for the footprint and a third of the weight of steel. The system needs an inhibitor rated for aluminium, which any installer will dose as standard.
Surface area wins. Aluminium panels, double panels and 3- or 4-column radiators all out-perform a single panel of the same width. For the largest rooms, two radiators are often better than one very large one.
No. A radiator uses no energy; bigger surface lets the heat pump run cooler, and every degree lower on the flow temperature improves its efficiency by roughly 2–3%.
Usually. Enter your pipe centres in the pipe-centre finder and it lists every radiator that drops onto the existing pipes exactly or with a pair of rigid tail extensions. Where the pipes do have to move, our plumber brief tells a heating engineer exactly what to do.
Across Lancashire (BB, PR, FY, LA1–LA6, L39, L40, WN8, OL12 and OL13 postcodes) our own Gas Safe registered engineers survey the rooms, size the radiators for the heat pump's design temperature and fit them, pipework moves included. Elsewhere in mainland UK, delivery is free and arrives within 48 hours of dispatch on stock lines, and the plumber brief gives your local installer the figures. Questions about a particular room? Get in touch and a heating engineer, not a salesperson, will answer.
Figures: radiator outputs from the manufacturers' EN 442 ratings as shown on each product page; heat-pump outputs are the ΔT50 rating multiplied by (30/50)^1.3 ≈ 0.515. Heat-loss ranges are typical values for UK housing and are no substitute for a room-by-room survey.