Most radiators sized for a gas boiler give only a third of their rated heat on a heat pump. Here is how to work out what each room needs, how much bigger the radiators have to be, and which types get you there without filling the wall. Written by the Gas Safe registered heating engineers at Bradleys Radiators. Last reviewed October 2026.
A radiator that heats a room perfectly on a gas boiler will usually give only a third to a half of that heat on a heat pump. The radiator hasn't changed; the water inside it has. A boiler sends water out at around 70–75°C. A heat pump sends it out at 35–55°C. And a radiator's output falls steeply as the water gets cooler.
That is why heat pump installers talk about "radiator upgrades", and why it is not a sales add-on. If the radiators stay as they are, the installer has to run the heat pump hotter to compensate, and running hot is exactly what makes a heat pump expensive. Correctly sized radiators let the system run cool, which is where a heat pump earns its efficiency and the grant pays off.
Every radiator output advertised in the UK, in watts or BTU, is measured at ΔT50 under the EN 442 standard. ΔT50 means the water in the radiator averages 50°C above the room: 75°C flow, 65°C return, a 70°C mean, in a 20°C room. That is a gas boiler running flat out, and it is the only condition the published number is true for.
A heat pump never runs there. A typical air source heat pump is designed around 45°C flow and 40°C return, a mean of 42.5°C. In a 20°C room that is ΔT22.5, less than half the temperature difference the radiator was rated at.
Output does not fall in a straight line with ΔT; it falls faster. At ΔT25 a radiator gives roughly 40% of its ΔT50 output, not 50%. To find your ΔT, add the flow and return temperatures, halve them, and take away the room temperature. If your installer only gives you a flow temperature, assume a 5°C drop across the radiator and a 20–21°C room.
Multiply any advertised ΔT50 output by the factor for your flow temperature to see what it will actually deliver. Or divide the room's heat loss by the factor to get the ΔT50 output you need to buy. Figures assume a 5°C drop across the radiator and a 20°C room.
| Flow / return (°C) | ΔT | Output factor | Radiator needs to be | Typical system |
|---|---|---|---|---|
| 75 / 65 | 50 | 1.00 | 1.0× (rating condition) | Gas boiler |
| 55 / 50 | 32.5 | 0.57 | 1.75× bigger | Hybrid or high-temperature heat pump |
| 50 / 45 | 27.5 | 0.46 | 2.2× bigger | Heat pump in an older house |
| 45 / 40 | 22.5 | 0.35 | 2.8× bigger | Most new air source installs |
| 40 / 35 | 17.5 | 0.26 | 3.9× bigger | Well-insulated house |
| 35 / 30 | 12.5 | 0.17 | 6.1× bigger | Underfloor heating territory |
Two things to take from this. First, a radiator on a 45°C system gives about a third of its label output, so a room that needed a 1,500 W radiator on a boiler now needs about 4,200 W of ΔT50 radiator. Second, there is a big difference between 45°C and 50°C flow: going 5°C cooler costs you roughly a quarter more radiator, but gains several points of heat pump efficiency every hour it runs.
If a 1,800 W room needs 5,000 W of ΔT50 radiator and the only free wall is 1,200 mm wide, that is a design conversation, not a shopping one. It is exactly what the survey visit is for.
A three-bed semi in Lancashire: cavity walls filled, loft insulated, double glazed, designed at −3°C outside and 21°C inside. The installer's heat loss and the resulting radiator sizes at 45/40 (factor 0.35):
| Room | Heat loss (W) | ΔT50 output to buy (W) | Existing radiator (typical ΔT50) | What fits |
|---|---|---|---|---|
| Living room | 1,800 | 5,150 | 600×1200 double panel, about 2,100 W | Two radiators: a 4-column horizontal under the window and a tall double vertical on the chimney-breast wall |
| Kitchen-diner | 1,500 | 4,300 | 600×1000 single panel, about 900 W | A 6-column horizontal, or a 1,800 mm double vertical with a second vertical if the wall is short |
| Bedroom 1 | 900 | 2,570 | 600×1000 single panel, about 900 W | 3-column horizontal, 600 mm high, around 1,400 mm wide |
| Bedroom 2 | 700 | 2,000 | 600×800 single panel, about 700 W | 3-column horizontal, 600 mm high, around 1,100 mm wide |
| Bathroom | 500 | 1,430 | Chrome towel rail, about 350 W | Keep the towel rail for towels; add a compact 3-column or a slim vertical to heat the room |
| Hall and landing | 1,100 | 3,140 | 600×1000 double panel, about 1,700 W | Tall double vertical, 1,800 mm, in the hall |
The existing radiators total about 6,650 W at ΔT50; the house needs about 18,600 W. Every radiator changes, and the total radiator surface roughly triples. That is normal for a house of this age. The alternative is running the heat pump at 55°C and paying for it every winter.
The job is to get three times the output into roughly the same wall space, so choose by output per metre of wall and by depth first, looks second.
| Radiator type | Output for the wall space | Verdict |
|---|---|---|
| 4 and 6 column | The highest of any traditional radiator; a 6-column gives roughly double a 3-column of the same height and width | Best choice for living rooms and kitchens. 4 and 6 column radiators need feet for support, so allow for them |
| 3 column | Good; comfortably above a double panel of the same width | Bedrooms, halls and dining rooms |
| Double vertical (flat or oval tube) | Very high output on a narrow footprint at 1,600–1,800 mm tall | The answer where the wall is short but tall: beside doors, on chimney breasts, in halls |
| Aluminium | High output per metre and low water content, so it responds in minutes | Excellent for heat pumps; the fast response suits weather compensation. Check the pipework can deliver the flow |
| Type 22 double panel | Fine, but bulky at the widths a heat pump needs | Acceptable on a tight budget; usually replaced by column or vertical for the same output in less width |
| Single panel, single column | Low | Rarely enough on a heat pump; replace |
| Heated towel rail | Low, and much of it goes into the towels | Keep for towels; do not rely on it to heat a bathroom |
| Cast iron | High output but very slow, with a large water volume | Works, but heavy and slow to respond |
Two more rules from survey experience. Put the biggest radiator in the room with the biggest heat loss, not the biggest wall. And don't worry about "too much" water volume: lots of large radiators is good for a heat pump, because system volume helps it run in long, steady cycles instead of short bursts.
The cooler you run, the less electricity the heat pump uses and the more radiator you have to buy. Roughly, every 1°C drop in flow temperature improves a heat pump's efficiency by 2–3%, so dropping from 55°C to 45°C is worth around 20–25% off the running cost for the same heat.
| Design flow | Radiators vs boiler sizing | Running cost | When it makes sense |
|---|---|---|---|
| 55°C | About 1.75× | Highest | Hard-to-insulate houses, microbore pipework, or where radiators can't be changed now |
| 50°C | About 2.2× | Noticeably better | Older houses where some radiators can be upgraded |
| 45°C | About 2.8× | The sweet spot for most UK homes | The default for a well-designed air source install in a typical insulated house |
| 40°C | About 3.9× | Better again | Well-insulated or newer homes with generous wall space |
| 35°C | About 6× | Best | Underfloor heating or very low-energy homes; rarely achievable with radiators alone |
A good installer designs the house at the lowest flow temperature the radiators can be made to work at within budget, then sets the weather compensation curve so the heat pump only runs that hot on the coldest days. Most of the winter it runs cooler still. That is why oversizing radiators is never wasted: it buys efficiency on every mild day of the year, not just the design day.
The Boiler Upgrade Scheme pays £7,500 towards an air or ground source heat pump in England and Wales, rising to £9,000 for homes currently heated by oil or LPG for applications made between 21 July 2026 and 31 March 2027. Your installer claims it and takes it off your quote, and you need an MCS-certified installer to qualify. The EPC requirement was removed in April 2026. Scotland runs a separate scheme through Home Energy Scotland. Terms change by budget year, so check the government page before you commit.
Radiators are normally included in the heat pump quote and covered within the same job, so have the radiator conversation before you sign, not after.
What a proper survey includes: a room-by-room heat loss to BS EN 12831, a design flow temperature, a radiator schedule showing each room's required and proposed ΔT50 output, a check of pipe sizes, and a check that the hot water cylinder and controls suit the heat pump. If a quote arrives without a radiator schedule, ask for one.
Not always, but in a pre-2000 house it is usual to replace most of them. A radiator that already delivered far more than its room needed on the boiler may survive. The heat loss calculation tells you which.
You can, but a double panel wide enough for a heat pump often won't fit the wall. Column and double vertical radiators give the same output in much less width, which is why they are the usual choice.
No. ΔT60 is a flattering test condition that overstates output by about 25% compared with the standard ΔT50. Always compare at ΔT50, and if a listing doesn't say which, assume the worse.
Yes. Output is output. A 1,800 mm double vertical gives as much heat as a wide horizontal with the same ΔT50 rating, and warms the room just as evenly once the system is running steadily, which a heat pump does.
Ask for the room-by-room heat loss and the design flow temperature and check them against the table above. Undersized radiators forcing a high flow temperature is the most common reason a heat pump costs more to run than promised.
Not meaningfully. Anthracite, black and white versions of the same radiator give the same heat within a few per cent.
Leave the valves on, but set the TRVs fully open in most rooms and let the heat pump's weather compensation control the temperature. TRVs closing down starve a heat pump of flow and make it cycle. Keep one or two rooms on a TRV only if they overheat.
Yes, and it is common: underfloor downstairs at around 35°C and radiators upstairs, usually with a mixing arrangement so the radiators get slightly warmer water.
Bradleys Radiators supplies the column, vertical and aluminium radiators that heat pump installers specify, with ΔT50 outputs stated on every product page, and we are a Gas Safe registered heating business ourselves. Send us your installer's heat loss figures and design flow temperature and we will put together a radiator schedule to match it, room by room, from stock. If you are in Preston or the Fylde, we can also survey and fit: enter your postcode on our installations page to check.